Museum Lighting: How Do We Calculate an Exhibit’s Light Exposure in Lux-Hours?

Calculating exhibit light exposure from illuminance and duration in different operating modes, recording measurements and respecting conservation limits.

2026-11-27

An exhibit’s light exposure is obtained by multiplying illuminance measured on its surface, in lux, by the lighting duration in hours. If the level changes during the day, calculate exposure for each interval separately and add the results. This accounts not only for lighting switched on for visitors, but also for work lighting and daylight.

What Do Lux-Hours Tell Us?

Lux describes illuminance at the moment of measurement. Lux-hours show how much light a surface has received over time. The Canadian Conservation Institute describes exposure as the product of illuminance and duration. The same number does not mean the same risk for every material: exhibit sensitivity, light spectrum and ultraviolet radiation need separate consideration. A conservator determines the permitted regime for a particular work.

Example: Public Opening Hours and Work Lighting

Suppose 50 lx is measured on a work in a display case during public opening hours, lasting 8 hours. After closing, during a separate half-hour cleaning period, the total illuminance measured on the exhibit is 200 lx. At other times, light in this example is close to zero.

- Public mode: 50 lx × 8 h = 400 lx·h. - Work mode: 200 lx × 0.5 h = 100 lx·h. - Daily total: 500 lx·h, or 25% more than an estimate based only on public opening hours.

These figures are a calculation example, not a recommended standard for an exhibit. If daylight overlaps with artificial lighting, measure their combined illuminance during that period; do not add daylight to the same measurement a second time.

How Do We Prepare a Useful Measurement Record?

1. Position the luxmeter sensor at the exhibit’s level and in the same plane, without shading the surface. If lighting is uneven, measure several points and record the brightest area too. 2. Record opening, closing, cleaning and installation modes separately. With variable daylight, use periodic measurements or a logging sensor rather than a single reading. 3. Record the measurement point, operating mode, time and duration. Compare the resulting total with the conservator’s limit for the same period.

If exposure is high, start by reducing unnecessary work-lighting hours. If illuminance is excessive at one point, check the accent luminaire’s optics and aiming, then measure again.

Sources

Project Context

Ready to Apply This in Your Space?

A final engineering solution requires an assessment of your space, intended use and existing infrastructure.